The InRow Chilled Water product design closely couples the cooling with the IT heat load. This design prevents hot air recirculation, while improving cooling predictability and allowing for a pay as you grow environment. Available with and without humidity control, these products are designed to meet the diverse requirements for medium to large data centers. Data center operators looking to improve efficiency or deploy high density servers will benefit from the modular design of the InRow Chilled Water products. The intelligent controls of the InRow Chilled Water products actively adjust fan speed and chilled water flow to match the IT heat load to maximize efficiency and address the dynamic demands of today's IT environments.
The InRow Direct Expansion product design closely couples the cooling with the IT heat load. This design prevents hot air recirculation, while improving cooling predictability and allowing for a pay as you grow environment. Available in self-contained, fluid cooled, and air-cooled configurations with or without humidity control, these products meet the diverse requirements for closets, server rooms, and data centers. IT operators looking to improve efficiency or deploy higher density equipment will benefit from the modular design of the InRow Direct Expansion products. The intelligent controls of the InRow Direct Expansion products actively adjust fan speed and refrigerant flow to match the IT heat load to maximize efficiency and address the dynamic demands of today's IT environments.
The InfraStruXure InRow SC
The InfraStruXure InRow SC is an air cooled, self-contained, cooling-only air conditioner designed to be placed in-row,
between equipment racks. The in-row design allows the SC to draw in air from the rear, capturing heat from the IT equipment
in the hot aisle and neutralizing it before it mixes with the room air. Conditioned air is then discharged into the cold aisle,
ready for immediate use by the equipment in the adjacent racks. The SC is a singled-corded device with input power provided
from 200-240V, 1Ø, 60Hz (ACSC100) or 200-240V, 1Ø, 50Hz (ACSC101) sources.
The unit’s refrigeration system is driven by a compressor which has a considerable in-rush current. Sizing a UPS to handle
this in-rush without going to bypass results in a significantly larger UPS then would be otherwise warranted to support the IT
load cooled by the InRow SC unit. Customers wishing to place the SC on the UPS must take the in-rush current into account,
to make their sizing decision. Additionally, for battery run-time calculations, the SC consumes up to 3 kW of power (2,940
watts for ACSC100, 2,390 watts for ACSC101) during normal operation.
|